Reducing energy costs and ensuring energy security,providing you with efficient solutions
● 3 Type Survey
Temperature, Smoke and Gas Detection
● 3-Tier Firefighting
PACK class + in-cabinet fire protection + water fire protection
● 3-level Control
Passive + Active + Passive
The addition of a hydrogen exhaust fan effectively prevents gas buildup and eliminates potential hazards.
Add a water fire interface to construct a final safety barrier.
● Standard cabinet design, partitioned isolation, liquid cooling technology + combustible gas detection and Heptafluoropropane fire protection technology ensure a safe and controllable system.
● Single string design, zero parallel loss; intelligent BMS+EMS fusion technology, high-efficiency three-level topology PCS technology to maximize the system conversion efficiency.
● Embedded with highly integrated EMS system, it realizes peak shaving and valley filling, demand control, emergency control, load tracking, global monitoring, fault recording and broadcasting; adapts to a variety of application scenarios; the operation data can be accessed to the cloud platform through WIFI, 5G, LAN, etc., realizing unattended operation.
● All-in-one design concept, integrating battery cell, BMS, PCS, fire protection system, power distribution system, thermal management system, energy management system in a standardized outdoor cabinet, forming an integrated plug-and-play one-stop integrated product. Turnkey solution; multiple machines can be connected in parallel to realize unlimited capacity expansion of the energy storage system.
Industrial & Commercial Integrated Cabinet - Homsun Energy Storage
• Certified to GB/T 36276-2023 (Latest National Standard)
• Product Liability Insured by Ping An Insurance
Product Parameters 100kW/215kWh
DC side | Battery | LiFePO4 | ||
Combination | 1P240S | |||
Nominal Capacity(Ah) | 280 | |||
Rated Energy(kWh) | 215 | |||
Rated Voltage(V) | 768 | |||
Rated Power(kW) | 100 | |||
Rated charge/discharge ratio | 0.5C | |||
Running Voltage(V) | 672~864 | |||
Standard C/D current(A) | 140/140 | |||
Cooling method | liquid cooling | |||
Coolant | C2H4(OH)2:water solution(50%v:50%v) | |||
Number of cycles | 8000 Times | |||
Fire Protection System | Perfluorohexanone | |||
Detector type | Temperature Sensitive, Smoke Sensitive, Flammable Gas | |||
AC side | Rated AC power(KVA) | 100 | ||
AC overload capacity(KVA) | 110 | |||
Wiring Method | Three-phase, Four-wire | |||
Allowable grid voltage | 380/400(-15%~15%)Vac | |||
Permissible grid frequency | 50/60(-2.5~2.5)Hz | |||
Total current harmonic distortion rate | <3% | |||
Power Factor | 0.99/-1~1 | |||
Operating voltage range(V) | 672~864 | |||
Voltage stabilization accuracy | ≤±1% | |||
Stabilization accuracy | ≤±1% | |||
Maximum conversion efficiency | 98.50% | |||
Cooling method | liquid cooling | |||
Systems | Charging operating temperature | -30℃~60℃ | ||
Discharge operating temperature | -30℃~60℃ | |||
Storage temperature | Short-term (within 1 month) | -30℃~60℃ | ||
Long-term (within 1 year) | 0℃~35℃ | |||
Vibration | <75dB | |||
Sizes(W×D×Hmm) | 935*1250*2340 | |||
Weights(T) | 2.2 | |||
Anti-corrosion grade | C3 C4 C5 (Selectable) | |||
Waterproof Level | Battery:IP65 Electric silo:IP54 | |||
Allowable relative humidity | 0-95%(Condensationless) | |||
Permissible Altitude(m) | ≤3000(3000+Reductions) | |||
System Efficiency | ≥86% | |||
Communication Interface | CAN,Ethernet | |||
Communication Protocols | ModbusTCP/RTU | |||
Operation Mode | Communication Protocols | ✔ | ||
Demand Control | ✔ | |||
ECO model | ✔ | |||
Reactive Power Regulation | ✔ | |||
Grid Dispatch Interface | ✔ | |||
Remote Dispatch Interface | ✔ | |||
Local Data Storage | ✔ | |||
Anti-backflow function | Optional | |||
Certification Standards | BMS | UL60730;GB/T34131-2017 | ||
Batteries | GB/T36276-2018;IEC62619;UL1973;UL9540A | |||
PCS | GB/T 34120-2017 | |||
Disclaimer: This product leaflet as far as possible on the basis of existing information comprehensive and detailed, the company reserves the right to modify the data, parameters and other information. The final explanation right belongs to Guangdong Homsun Electric Storage New Energy Co.